• Parameters

  • Details

  • Size&weight

  • Related

  • Video

  • Message

Scope of Application

DZ47S-125 Miniature Circuit Breaker (known as shunt trip MCB, 100 amp Circuit Breaker shunt trip). The shunt trip MCBis suitable for the control line of AC 50Hz or 60Hz, rated voltage 230V/400V, rated current of 125A and below, remote control and automatic signal breaking control for the line, is mainly used for over-load and short-circuit protection in circuits. And infrequent transfer between circuits in normal condition. Currently the shunt trip MCB is widely used in single-phase/ three-phase intelligent prepaid energy meter (such as IC card) to achieve the on-off of control lines. The series of products have high breaking capacity, small size, light weight, parts versatility, beautiful appearance, etc., it is mounted on the rail and easy to use.
DZ47S-125 shunt trip MCB comply with standards of GB10963.1, IEC60898-1.

Main Technical Parameters

Rated Current63A,80A,100A,125A
Poles1P+N,3P+N
Rated Voltage Ue230V/400V
Delay action time (Intelligent shunt tripping time)0.5s~2s
Rated Impulse Withstand Voltage(1.2/50)Uimp6kV
Dielectric Test Voltage At And Ind . Freq . For 1min2kV
Protection ClassIP20
Thermo - Magnetic Release CharacteristicC-Curve (5-10In)
Electrical Life2000
Mechanical Life10000
Reference Temperature For Setting Of Thermal Element30℃
Ambient Temperature-30~+60℃
Terminal Connection TypePhillips Screws
Adapter Cable6-63A 1-25mm² 16-3AWG | 80-125A 8-35mm² 16-2AWG
Tightening Torque3.0N.M
Combination With Accessories Auxillary Contact
Auxillary ContactYes
Alarm ContactYes
Shunt ReleaseYes
Under Voltage ReleaseYes

Tripping Characteristic Curve -- C Type


Temperature compensation

When the ambient temperature is not a benchmark of 30 degrees , the reference correction factor is as folows .

Ambient Temperature-20℃-10℃0℃10℃20℃30℃40℃50℃60℃
Current Correction Coefficient1.251.21.151.101.051.000.950.900.85

Connection

Rated CurrentMinimum Adapter Copper Wire
6A1 MM² / 17AWG
10A1.5 MM² / 16AWG
16A1.5 MM² / 16AWG
25A2.5 MM² / 13AWG
32A4 MM² / 11AWG
40A6 MM² / 10AWG
50A10 MM² / 7AWG
63A10 MM² / 7AWG
80A16 MM² / 5AWG
100A25 MM² / 4AWG
125A35 MM² / 2AWG

Mounting Method

1. Installed With 35MM Guide Rails.
2. Install With 3*25MM Screws On The Side
3. Install With Circuit Breaker Box.

view and download

File name(Click to view)File typefile sizeView timesClick to download

Product related news

News titlePromulgatorRelease timeView timesClick to read