• Parameters

  • Details

  • Size&weight

  • Related

  • Video

  • Message

Scope of Application

TXGV2 Molded Case Circuit Breaker (also known as motor protection circuit breaker, MPCB Circuit Breaker), is the new circuit breakers using international advanced design and manufacturing technology to research and develop. TXGV2 motor protection circuit breaker (MPCB Circuit Breaker) has a small size, high breaking current, short arc, anti-vibration. The rated insulation voltage is 750V, applies for the circuit of AC 50Hz, rated current of 0.1A-80A, for protecting overload, open phase, short-circuit and infrequent start of three-phase squirrel cage induction motor. TXGV2 motor protection circuit breaker (MPCB Circuit Breaker) can be used for distribution circuit protection and infrequent load conversion, also for isolation.
TXGV2 motor protection circuit breakers (MPCB Circuit Breaker) meet the standards: IEC60947.2, GB14048.2, GB14048.4.

Model and meaning

Main technical parameters

Operation: Button type
Rated insulation voltage: 750V
Rated operating voltage: 690V
Rated impulse withstand voltage Uimp: 6kV
Rated operating voltage Ue: 230 / 240V, 400 / 415V, 500V, 690V
Rated frequency: 50 / 60Hz
Frame rated current: 32A
Trip rating: 10A
Tightening torque: 1.7N • m
Mechanical life (on / off): 100000
Electrical life AC-3 400V: 100000
Overload protection category: thermal overload, phase-failure
Short-circuit protection: Yes
Isolation function: Yes
Temperature compensation function: Yes

No. Rated current of release
In A
Adjusting range of thermal element setting current
A
Rated ultimate short-circuit breaking capacity Icu(kA)/
Rated operation short circuit breaking capacity Ics(kA)
Flashover distance
mm
230/240V 400/415V 500V 690V
Icu Ics Icu Ics Icu Ics Icu Ics
1 TXGV2-32 0.16 0.1-0.16 100 100 100 100 100 100 100 100 50
2 0.25 -0.25 100 100 100 100 100 100 100 100
3 0.4 0.25-0.4 100 100 100 100 100 100 100 100
4 0.63 0.4-0.63 100 100 100 100 100 100 100 100
5 1 0.63-1 100 100 100 100 100 100 100 100
6 1.6 1-1.6 100 100 100 100 100 100 100 100
7 2.5 1.6-2.5 100 100 100 100 100 100 3 2
8 4 2.5-4 100 100 100 100 100 100 3 2
9 6.3 4-6.3 100 100 100 100 50 50 3 2
10 10 6-10 100 100 100 100 10 10 3 2
11 14 9-14 100 100 6 2 6 2 3 2
12 18 13-18 100 100 6 2 6 2 3 2
13 23 17-23 50 50 6 2 6 2 3 2
14 25 20-25 50 50 6 2 6 2 3 2
15 32 24-32 50 50 6 2 6 2 3 2

Outline and installation dimensions