Scope of Application

Take TXCPS as a switch, combined with contactors, electrical interlocks and other accessories to form TXCPSD Electrical Control Box (double speed electric controller), suitable for control and protection of double-speed motor.
Configurations of TXCPSD Electrical Control Box have three kinds:
Configuration 1: high-speed is the fire-type (overload, over-current with alarm and no trip), low-speed is the basic type;
Configuration 2: high, low speed are basic type;
Configuration 3: high, low speed are fire type (should specify the special order).
Features, the main circuit parameters and accessories module are the same as the basic type.

Models and Specifications

Outline and installation dimensions

Operation and control circuit diagram of TXCPSD Electrical Control Box

secondary power power protection Power model

fire valve

limit switch

Low speed local

and remote manual

control and interlock

Running signal Low speed alarm signal Stop signal High and low speed stop control

Adjust local and

remote manual control

and interlock

Running signal High speed alarm signal Stop signal High speed running contactor
Short circuit Fault Short circuit Fault

Note:
① This graph is suitable for the operation control of all kinds of TXCPSD Electrical Control Box, use both local and remote manual control.
② Control protector for high-speed smoke exhaust (2KBO), can choose fire type products, with functions of overload, over-current to only alarm not trip, short circuit to trip, to continue to work when overload. Secondary control schematic is in common use.
③ Introduced high and low speed start-stop button group can be installed on the box surface or wall.
④ The SQ, as the fire valve limit switch, the action device stops running; Short circuit occurs in the line without the fire valve limit switch.

No. Symbol Name Models and Specifications Quantity Remark
1 FU Fuses RT18-32X/4A 1 With fuse indication
2 CPS1.2 Control protector CPS-□□/□□/□□□ 2 See Selection Chart
3 HG1.2 Green light AD11-22/20~220V 2 Increase or decrease as required
4 HR1.2 Red light AD11-22/20~220V 2 Increase or decrease as required
5 HB1.2 Blue light AD11-22/20~220V 2 Increase or decrease as required
6 HY1.2 Yellow light AD11-22/20~220V 2 Increase or decrease as required
7 HW White light AD11-22/20~220V 1 Increase or decrease as required
8 SF1.2,SS1.

High and low speed

start-stop button

LAY(1 normally open and

1 normally closed)

3

One each for red,

green and yellow

9 SF3.4,SS2.

Introduced high and low

speed start-stop button group

Decided by engineering design 1