    DZ47S-63 Miniature Circuit Breaker with shunt trip (DZ47-60 Circuit Breaker), suitable for AC 50Hz (or 60Hz), rated voltage 230 / 400V, rated current 63A of the line, remote control and automatic signal breaking control for the line, is mainly used for over-load and short-circuit protection in circuits. And infrequent transfer between circuits in normal condition. Currently widely used in IC card prepaid watt-hour meter to control on-off of lines.
    DZ47-60 Circuit Breaker with shunt trip(60 amp MCB) has a small size, easy installation, etc., controls residential charged meter, when the IC card recharge balance is insufficient, the control circuit breaker will automatically disconnect to play the role of power outages, and users can close the circuit after recharging.
    Main functions: overload protection, short circuit protection, isolation, accept the IC card power meter signal to cut off the circuit.
    DZ47S-63 Miniature Circuit Breakers with shunt trip(DZ47-60 Circuit Breaker) meet standards of IEC60898, GB10963, GB14048.2, with the international advanced level.

    Model and meaning

    Technical parameters of DZ47S-63 MCB (DZ47-60 Circuit Breaker with shunt trip)

    ■ Rated current: 6, 10, 16, 20, 25, 32, 40, 50, 63A
    ■ Pole: 1P + N / 3P + N
    ■ Rated operating voltage: (1P + N) 230V; (3P + N) 400V
    ■ Frequency: 50Hz
    ■ Operating voltage range: (65% ~ 120%) Un
    ■ Breaking capacity: 230V (1P + N), 400V (3P + N);
    ■ Delay action time (intelligent shunt tripping time): 0.5s ~ 2s
    ■ Reset time: <30s
    ■ Mechanical life: 20,000 times
    ■ Electrical life: 4000 times, COSΦ = 0.85 ~ 0.9;
    ■ Current Limit Level: 3
    ■ Impulse withstand voltage: 6kV
    ■ Usage ambient temperature: -25 ℃ ~ 70 ℃
    ■ Resistance to heat and humidity: Class 2 (relative humidity 95% at 55 ° C)
    ■ Wiring: Terminal Wiring Area
      □ 6-32A, for 20mm ² and below of the wire
      □ 40-63A, for 25mm ² and below of the wire
      □ Tunnel-type terminal block, up and down locking clamp, easy to install. Terminal tightening torque is 2.0N · m.
    ■ Signal connection wire
      □ The signal line is located at the bottom of the circuit breaker
      □ Independent signal line cross-sectional area is 0.3mm ², length is 1000mm, length can be customized according to customer demand
    ■ Standards: GB10963.1, IEC60898-1
    ■ Certification: CCC
    ■ Tripping characteristics: Type C curve
      □ Protect the conventional load and distribution cables
      □ Characteristic: instantaneous trip range (5 ~ 10)In

    Normal operating conditions and installation conditions

    Ambient temperature: -25 ℃ ~ +60 ℃;
    Altitude: The altitude of the installation site does not exceed 2000m;
    Installation categories: Ⅱ, Ⅲ grade;
    Installation: Mounted on the TH35-7.5 steel rail.

    Over-current protective feature of DZ47S-63 MCB (DZ47-60 Circuit Breaker with shunt trip):

    No. Rated current Initial state Test current Set time Prosrective result
    1 All value Cold 1.13In t≤1h Non tripping
    2 All value Then after the last test 1.45In t<1h Tripping
    3 In<32 Cold
    2.55In 1s<t<60s Tripping
    In<32 1s<t<120s
    4 All value Cold 5In t≤0.1s Non tripping
    10In t<0.1s Tripping

    The shunt tripping characteristics:

    Model Rated control voltage Action time Repeat operation interval time

    DZ47S-63

    (60 amp MCB)

    230V~ 0.5s 3min
    Rated current In(A) Copper conductor nominal cross-sectional area(mm²)
    10 1.5
    16、20 2.5
    25 4
    32 6
    40、50 10
    63 16

    The current correction value used at different ambient temperatures

    Temperatures(℃)
    Corrected current value
    Rated current(A)
    -25 -20 -10 0 10 20 30 40 50 60
    10 12.5 12.4 11.9 11.3 10.8 10.4 10 9.7 9.2 8.5
    16 20 19.8 18.9 18.1 17.3 16.5 16 15.5 14.6 13.8
    20 25 24.8 23.6 22.6 21.1 20.6 20 19.4 18.2 17.2
    25 31.25 31 29.5 28.3 27 25.8 25 24.3 22.8 21.3
    32 40 39.7 37.8 36.2 34.6 33 32 31 28.8 27.2
    40 50 49.6 47.2 45.2 43.2 40.8 40 38.4 37.2 35.2
    50 63.5 62.5 59 56.5 54 51.2 50 48 45.5 43
    63 80.01 78.8 74.3 71.2 68 64.9 63 60.5 57.3 54.2

    Overload current tripping characteristic curve

    Structure and working principle

    Application example:

    Structure:

    DZ47-63 MCB is mainly composed of insulation case, operating system, contact system, thermal magnetic system and arc extinction system and other components. Signal control release consists of the signal input port, signal voltage detection circuit, delay control circuit and the trip mechanism and so on. MCCB and the signal-controlled trip have linkages by the pushrod.

    Working principle:

    By the signal input port, the circuit breaker signal control release is added control voltage, witch is the signal voltage (which can be provided by the remote control circuit), and then push the breaker handle to the closed position, through the operating mechanism to make the moving contact operate to the static contact and contact with the static contact, then the line connected. When the line has overload fault, the overload current make bimetallic element bend, overload release action promotes the locking mechanism action to achieve breaking the line. When the line has short-circuit fault, the short-circuit current makes instantaneous release act, to promote the locking mechanism to achieve breaking function. When due to some need to immediately cut off the line, which can cut off control voltage by the remote control system, the signal voltage detects circuit and obtains the signal, then outputs the voltage signal to the trip coil to make the locking mechanism act and realize the breaking function. So the product in different line state can achieve the purpose of breaking.

    Structural features

    Circuit breaker with shunt trip device, has the following characteristics:
    On-off neutral pole is faster on and slower off than the current protection pole;
    High rated breaking capacity, up to 6kA;
    The operating mechanism of the circuit breaker is the free tripping mechanism with energy storage. The contact is quickly closed, which overcomes the adverse effect caused by the speed of manpower operating handle, greatly improving the service life of the product. In normal work, the contact can only stay in the on or off position;
    Shunt release consists of the SCR, electromagnetic release and so on;
    Case and components are made of plastic of the high flame retardant, high temperature, impact resistant.

    Wiring: 25mm² and below for wire connection, wiring method is screws to tighten the wiring, the torque is 2.0N · m.

    Rated current In(A) Copper conductor nominal cross-sectional area(mm²)
    1~6 1
    10 1.5
    16~20 2.5
    25 4
    32 6
    40~50 10
    63 16